LDG-40 electromagnetic flowmeter
Category:
Instrumentation/Flow meter/electromagnetic flowmeter
Model:
LDG-40
Brand:
Jiangsu Fenghui Instrument Co., Ltd
Retail Price
1,500.00USD
重量
kg
- Product Description
-
Description :
This product can output standard current signals for recording, adjusting, and controlling purposes, achieving automatic detection and control, and can also achieve long-distance signal transmission.
1、 Technical parameters:
Nominal diameter (mm) (special specifications can be customized)
Pipeline type PTFE lining: DN10~DN600
Pipeline rubber lining: DN40~DN2200
Flow direction: positive, negative, net flow
Range ratio: 150:1
Repetitive error: ± 0.1% of the measured value
Accuracy level: Pipeline type: 0.5 level, 1.0 level
Temperature of the tested medium: ordinary rubber lining: -20 to+60 ℃; High temperature rubber lining: -20 to+90 ℃
PTFE lining: -30 to+100 ℃; High temperature PTFE lining: -20 to+180 ℃
Rated working pressure: (high pressure can be customized) DN10- DN150: ≤ 1.6MPa; DN200-DN350:≤1.0MPa
DN400-DN1000:≤0.6MPa; DN450-DN2200:≤0.25MPa
Flow velocity range: 0.1-15m/s

2、 Selection of installation location:
1. The flow direction indicator on the sensor must match the direction of the measured medium flow inside the pipeline.
2. The installation position must ensure that the measuring tube is filled with the measured medium.
3. Choose a location with smaller fluid flow impulse, which should be away from the pump and local resistance components (valves, elbows, etc.)
4. When measuring two-phase fluids, a location that is not prone to phase separation should be selected.
5. Installation in areas with negative pressure inside the pipe should be avoided as much as possible.
6. When the measured medium easily causes adhesion and scaling on the inner wall of the electrode and measuring tube, it is recommended that the flow velocity inside the measuring tube should not be less than 2m/s.
3、 Characteristics:
The measurement of flow rate is not affected by changes in fluid density, viscosity, temperature, pressure, and conductivity. The sensor induced voltage signal is linearly related to the average flow rate, resulting in high measurement accuracy (0.3-0.5%).
There is no obstruction in the measuring pipeline, so there is no additional pressure loss, which has significant energy-saving significance.
There are no movable parts inside the measuring pipeline, so the sensor has a long lifespan.
The straight pipe section required for the sensor is relatively short, making it easy to install.
Reasonable selection of electrode and lining materials can resist corrosion and wear.

AfterSalesService :
Key words:- LDG-40 electromagnetic flowmeter