Integrated LDG electromagnetic flowmeter LDG-100 anti-corrosion electromagnetic flowmeter
Category:
Instrumentation/Flow meter/electromagnetic flowmeter
Model:
LDG-100
Brand:
Jiangsu Fenghui Instrument Co., Ltd
Retail Price
1,800.00USD
重量
kg
- Product Description
-
Description :
This product has the advantages of good reliability, stability, complete functions, and long service life. It can measure the volumetric flow rate of conductive liquid media in closed pipelines, including strong corrosive liquids such as acids, alkalis, salts, mud, sewage, and solid-liquid suspensions.
1、 Characteristics:
The measurement of flow rate is not affected by changes in fluid density, viscosity, temperature, pressure, and conductivity. The sensor induced voltage signal is linearly related to the average flow rate, resulting in high measurement accuracy.
There is no obstruction in the measuring pipeline, so there is no additional pressure loss; There are no movable parts inside the measuring pipeline, so the sensor has an extremely long lifespan.
Due to the fact that the induced voltage signal is formed in the entire space filled with a magnetic field and is the average value on the surface of the pipeline, the sensor requires a shorter straight pipe section, with a length of 5 times the diameter of the pipeline.
The sensor part only has the inner lining and electrodes in contact with the measured liquid. As long as the electrode and inner lining materials are selected reasonably, they can be corrosion-resistant and wear-resistant.
2、 Technical parameters:
Nominal diameter (mm) (special specifications can be customized)
Pipeline type PTFE lining: DN10~DN600
Pipeline rubber lining: DN40~DN2200
Flow direction: positive, negative, net flow
Range ratio: 150:1
Repetitive error: ± 0.1% of the measured value
Accuracy level: Pipeline type: 0.5 level, 1.0 level
Temperature of the tested medium: ordinary rubber lining: -20 to+60 ℃; High temperature rubber lining: -20 to+90 ℃
PTFE lining: -30 to+100 ℃; High temperature PTFE lining: -20 to+180 ℃
Rated working pressure: (high pressure can be customized) DN10- DN150: ≤ 1.6MPa; DN200-DN350:≤1.0MPa
DN400-DN1000:≤0.6MPa; DN450-DN2200:≤0.25MPa
Flow velocity range: 0.3-15m/s

3、 Installation:
1. It should be installed indoors in a dry and ventilated area. Avoid installation in areas with high ambient temperatures, avoid strong vibrations, and try to avoid equipment with strong magnetic fields. Such as large motors, transformers, etc. Avoid installation in environments with corrosive gases. The installation location should be convenient for maintenance, which is the environmental condition to ensure the normal operation of the transmitter.
2. Valves and bypasses should be installed at both ends of the electromagnetic flow transmitter.
3. In order to ensure that the measuring tube of the electromagnetic flow transmitter is filled with the measured medium, it is installed vertically and flows from bottom to top. Especially for liquid-solid two-phase flow, it must be installed vertically. If only horizontal installation is allowed on site, it must be ensured that the two electrodes are on the same horizontal plane.
4. To avoid interference signals, the signal between the transmitter and the converter must be transmitted using shielded wires. It is not allowed to parallel signal cables and power lines in the same cable steel pipe. The length of signal cables should generally not exceed 30m.