Nanjing LDG-350 electromagnetic flowmeter
This product is used for flow measurement of various conductive liquids in industrial engineering, such as corrosive media such as acids, alkalis, salts, etc; Various flammable and explosive media; The measurement of various slurry flow rates in wastewater treatment, chemical, food, pharmaceutical and other industries has formed a unique application field.
1、 Structure
The product structure mainly consists of magnetic circuit system, measuring conduit, electrode, shell, lining, and converter.
2、 Performance indicators
Flow velocity measurement range: (0.05-10) m/s
Power consumption:<15VA
Protection level: IP68
Connection method: flange connection
Electrode materials: molybdenum containing stainless steel OCr18Ni12Mo2Ti, Hastelloy B, Hastelloy C, titanium Ti, tantalum, etc
Measuring pipeline diameter: DN (32-6000) mm
Instrument accuracy: Level 1.0
Work pressure: ≤ 1.6MPa
Medium temperature: 0-80 ℃

Nanjing LDG-350 electromagnetic flowmeter
3. Installation
1. Horizontal and vertical installation
Sensors can be installed horizontally and vertically, but it should be ensured to avoid the influence of sediment and bubbles on the measuring electrode, and the electrode axis should be kept horizontal. When installed vertically, the fluid should flow from bottom to top. Sensors cannot be installed at high positions in pipelines, as this location is prone to the accumulation of air bubbles.
2. Ensure full pipe installation
Ensure that the flow sensor is filled with the measured fluid in the pipeline during measurement and that there is no non full pipe state. If the pipeline is not full or the outlet is empty, the sensor should be installed on a siphon tube.
3. Installation between bends, valves, and pumps
To ensure the stability of the measurement, a straight pipe section should be installed before and after the sensor, with its length given. If it cannot be achieved, a current stabilizer should be used or the cross-sectional area of the measurement point should be reduced.
4. Sensors cannot be installed at the inlet of the pump
To avoid negative pressure, the sensor should not be installed at the inlet of the pump, but at the outlet of the pump.