LWGY-25 turbine flowmeter
LWGY-25 turbine flowmeter

LWGY-25 turbine flowmeter

Category:

Instrumentation/Flow meter/Turbine flow meter

Model:

LWGY-25

Brand:

Jiangsu Fenghui Instrument Co., Ltd

Retail Price

985.00USD


重量

kg

  • Product Description
  • Description :

      LWGY-25 turbine flowmeter

      This product is a precision flow measurement instrument that can be used to measure the flow rate and total amount of liquids when paired with corresponding flow accumulation instruments. detailed introduction

      1、 Working principle:

      The turbine inside the sensor rotates under the action of fluid, causing a change in the magnetic field of the signal detector. Therefore, an alternating voltage is induced in the coil of the signal detector, which is amplified, filtered, and shaped by an amplifier to output a square wave signal. The frequency of this signal voltage is directly proportional to the speed of the impeller, that is, directly proportional to the flow rate (velocity) of the fluid.

      2、 Technical parameters:

      Nominal diameter: Pipeline type: DN4~DN200

      Accuracy level: Pipeline type: ± 0.5 level, ± 1.0 level

      Insertion type: ± 1.5 level, ± 2.5 level

      Environmental temperature: -20 ℃~50 ℃

      Medium temperature: Measuring liquid: -20 ℃~120 ℃

      Measurement gas: -20 ℃~80 ℃

      Atmospheric pressure: 86KPa~106KPa

      Nominal pressure: 1.6 Mpa, 2.5 Mpa, 6.4 Mpa, 25 Mpa

      Explosion proof grade: ExdIIBT4

      Liquid: The upstream straight pipe section should be ≥ 20DN, and the downstream straight pipe section should be ≥ 5DN

      LWGY-25 turbine flowmeter

      3、 Installation:

      1. The instrument installation adopts flange connection, threaded connection and clamping type;

      2. The direction of liquid flow during installation should be consistent with the direction indicated by the arrow on the sensor housing, and the upstream straight pipe section should be ≥ 6DS, and the downstream straight pipe section should be ≥ 5DS (DS is the measured inner diameter of the tested pipeline).

      3. Sensors should be kept away from external magnetic fields. If unavoidable, necessary measures should be taken;

      4. In order to avoid affecting the normal transportation of liquids during maintenance, bypass pipelines should be installed outside the straight pipe sections at both ends of the sensor;

      5. When installing sensors outdoors, please ensure that the amplifier plug is waterproofed;

      6. The wiring between sensors and display instruments should be selected based on the power supply of the amplifier. 1. The instrument installation adopts flange connection, threaded connection and clamping type;

      2. The direction of liquid flow during installation should be consistent with the direction indicated by the arrow on the sensor housing, and the upstream straight pipe section should be ≥ 6DS, and the downstream straight pipe section should be ≥ 5DS (DS is the measured inner diameter of the tested pipeline).

    AfterSalesService :