Used for new energy JOSEF Joseph trip relay GRUS-11T-9H4D/125VDC
Category:
electron/electrical/Liquid level controller
Model:
GRUS-11T-9H4D/125VDC
Brand:
Shanghai Joseph
model:
GRUS-11T-9H4D/125VDC
Processing & Customization:
yes
rated voltage:
two hundred and twenty
Place of Origin:
Shanghai
manufacturer:
Shanghai Joseph
Retail Price
320.00RMB
重量
kg
- Product Description
-
model GRUS-11T-9H4D/125VDC
Processing & Customization yes
rated voltage two hundred and twenty
Place of Origin Shanghai
manufacturer Shanghai Joseph
Description :
GRUS-11T series LOCKOUT interlock tripping relay
GRUS-11T-9H4D/220VDC
GRUS-11T-10H3D/220VDC
GRUS-11T-9H4D/125VDC
GRUS-11T-10H3D/125VDC
GRUS-11T-9H4D/110VDC
GRUS-11T-10H3D/110VDC
GRUS-11T-5H2D\DC220V
GRUS-11T-3H3D-6H1D\220V
GRUS-11T-3H3D-6H1D\110V





Application scenarios and characteristics
LOCKOUT relay, also known as lockout trip relay
This relay is suitable for use in conjunction with generator transformer protection or transformer protection, with up to 13 pairs of contacts for fast tripping outlets, signaling, and other functions
Used for situations where the auxiliary contacts of a single device cannot meet the required quantity and need to be expanded, it can be reset remotely or locally
PHOENIX MSTB series terminals are selected for wiring terminals
Installation dimensions: EMG-GCP: 146mm (L) × 72.5mm (W) × 115.5mm (H)
Installation method: Embedded installation
Terminal block: can be disassembled and assembled with a Yiyu screwdriver
Product Series
GRUS=Embedded Operation Relay Function Definition
11T=plastic EMG/GCP structure, a pair of normally closed contact relay output contact types
9H4D=Nine normally open and four normally closed contacts
10H3D=rated working voltage of relay coils with ten normally open contacts and three normally closed contacts
220VDC=220V rated DC voltage; 125VDC=125V rated DC voltage; 110VDC=110V rated DC voltage
Input circuit - coil voltage rated DC voltage 110VDC; 125VDC; 220vDc
Allow long-term working voltage of 1.2Un
Reliable action pulse width ≥ 50mS
Starting voltage range 50% to 80%
Output circuit - relay contact output
Number of contacts: Thirteen pairs of contacts
Output contact type 9H4D; 10H3D
Contact point for long-term connection of load current 8A@250VAC /30vDc
Action time (rated voltage) ≤ 7mS (normally open contact closing time)
Return time (normally open contact return) ≤ 15mS (normally open contact return)
Insulation resistance ≥ 100MQ
Dielectric strength 2000VAc, 50Hz, 1min, 5mA between coil and contact
The overall power consumption of the product is ≤ 3W
Tightening torque 0.5~0.6Nm
Working environment -40 ℃~+70 ℃. 5%~95% without condensation
Screw, gasket, and terminal material: copper material
Storage environment -40 ° C~+85 ° C. 5%~95% no condensation
Insulation resistance: The insulation resistance of each conductive circuit to ground and between conductive circuits shall not be less than 100MQ
Dielectric strength AC 2Kv, 1min, leakage current 5 mA
Impulse voltage 1.2/50us, ± 5KV, 3 times

Key words:- Trip relay