JOSEF LLJ-1000FG Leakage Relay Hardware Tools

JOSEF LLJ-1000FG Leakage Relay Hardware Tools

Category:

electron/electrical/Liquid level controller

Model:

LLJ-1000FG

Brand:

Shanghai Joseph

model:

LLJ-1000FG

Processing & Customization:

yes

rated voltage:

two hundred and twenty

Place of Origin:

Shanghai

manufacturer:

Shanghai Joseph

Retail Price

120.00RMB


重量

kg

  • Product Description
  • model

    LLJ-1000FG

    Processing & Customization

    yes

    rated voltage

    two hundred and twenty

    Place of Origin

    Shanghai

    manufacturer

    Shanghai Joseph

    Description :

      LLJ-15FG leakage relay; LLJ-63FG leakage relay

      LLJ-120FG leakage relay; LLJ-100FG leakage relay

      LLJ-200FG leakage relay; LLJ-250FG leakage relay

      LLJ-400FG leakage relay; LLJ-500FG leakage relay

      LLJ-320FG leakage relay; LLJ-630FG leakage relay

      LLJ-1000FG leakage relay;

      1、 Product Usage and Characteristics

      The LLJ-FS series leakage relay (hereinafter referred to as the relay) is suitable for use in AC voltage systems ranging from 660V to 1140V, with a frequency of 50Hz and a current of 15~4000A. It is used to determine whether there is a neutral point in the circuit

      Leakage protection This relay can be used to form a leakage protection device with circuit breakers, AC contactors, magnetic starters, etc. equipped with shunt release or voltage loss release, for the purpose of leakage and electric shock protection

      A leakage alarm device is composed of various sound and light indicating devices such as buzzers and signal lights.

      LLJ relay is divided into guide rails There are two installation methods for the panel Small size, easy to use, fixed or adjustable action values, reliable action, stable continuous power supply, and easy operation. Can adapt to users from all over the world,

      It can be used for ground fault protection of power lines to prevent equipment accidents or electrical fires caused by ground fault currents, and can also be used to provide indirect electric shock protection for human electric shock relief. it

      Suitable for low-voltage distribution systems with direct grounding at the center point of the power system or underground coal mine distribution systems without neutral grounding, it is a safe new product for network transformation. The action time of this relay is fast

      Speed type and delay type, when used together, provide graded protection for main and branch lines.

      2、 Working principle

      This relay is an electronic current operated leakage relay, mainly composed of a zero sequence current transformer electronic circuit, a test circuit, and an outlet relay. Its working principle is as follows: the wiring is shown in the diagram on the right, and when passing through

      When there is ground leakage in the circuit of the zero sequence current transformer, iAtiB+iC+iN head will be 0, and an induction signal will be generated on the side of the zero sequence current transformer. This signal is processed by an electronic circuit, and when the leakage current reaches

      When the action value is reached, the thyristor is turned on, the outlet relay is activated, and the main circuit breaker or contactor is controlled to disconnect using normally open and normally closed contacts, thereby achieving the purpose of protection. The experiment is carried out by resistance

      Composed of buttons and other components, when the button is pressed, current flows through the transformer, which is equivalent to leakage in the main circuit, and the product should be activated.

      3、 Technical data

      Rated voltage: 380660690

      Rated leakage current (mA): 30mA~500mA User selected

      Rated leakage non operating current (mA): 15mA-250mA User selected

      Fast action time type: ≤ 0.1S

      Action time delay type: 0.1~1s

      Contact capacity: 220V5A

      Action current 30~500mA

      Zero sequence aperture: 25mm~220mm

      Host size: 88 * 36 * 60mm

      4、 Model meaning

      S: Delay type (no S for fast type)

      T: Installation method: T represents embedded panel type

      Leakage relay is a type of device that detects circuit contact (leakage) and sends a mechanical opening and closing signal to the control circuit device. It can be combined with various specifications of low-voltage circuit breakers or AC contactors to form a residual current operated protector. Nowadays, a relatively complete rural low-voltage power grid classification (second or third level) leakage protection mode has been achieved, which has become an important component of the overall line protection device and plays an important role in preventing line and equipment leakage and personal electric shock.

      Due to the use of residual current relays for equipment protection, their safety performance should be able to be tested. For this purpose, a test button is added to the leakage relay to test its protective performance. When the button is pressed, a test current flows through the magnetic ring, and the leakage relay should act quickly. If the leakage relay does not operate, it indicates that there is a fault and it must be stopped immediately. The commonly used residual current device is equivalent to a combination of automatic switch and residual current relay, mainly used for personal safety protection. The human body can feel a current of 2 mA when exposed to 50 Hz AC power, while a current of 30 mA or higher can be fatal. Therefore, when selecting, attention should be paid to the magnitude of the operating current of the leakage protector. In order to reliably operate under small signals, the leakage protector is equipped with an electronic circuit that ignites small signals.

    Key words:
    • Leakage relay