Open type current transformer for energy-saving renovation
Open type current transformer for energy-saving renovation

Open type current transformer for energy-saving renovation

Category:

Electrical Engineering/Complete electrical and electrical equipment/Other electrical and electrical equipment

Model:

ARTM

Brand:

Acrel

Retail Price

300.00USD


重量

kg

  • Product Description
  • Description :

      AKH-0.66K Open Type Current Transformer

      Selection and installation methods

      Select the corresponding specification product based on parameters such as primary current and busbar cross-section. A wire passes through the transformer window once. Open the flip cover, perform secondary wiring through the crimping piece, and reset the flip cover after the secondary wiring is led out. Measuring electrical energy can be directly achieved by sealing the small holes on the flip cover with lead seals to prevent electricity theft.

      The working current shall not exceed 1.1 times the rated value for a long time, and it is allowed to be used for a short time at 1.2 times the rated value for no more than 1 hour;

      According to the magnitude of the measured current, select the rated current ratio, generally choosing a rated current that is about 2/3 larger than the measured current;

      The polarity of the product is represented by the primary wiring symbols P1 and P2, and the corresponding secondary wiring symbols S1 and S2; S1 represents the same named end of P1, and S2 represents the same named end of P2;

      The measuring instrument is connected to terminals S1 and S2. At this time, the total load of the connected circuit should not exceed the rated load of the transformer. When the installation location of the instrument is far away from the current transformer or the circuit load is large, the secondary current specification of 1A should be preferred;

      Pay attention to selecting transformers with matching window sizes based on the specifications and number of busbars.

      1 Product Introduction

      Function:

      The AKH-0.66K series open type current transformer is easy to install and does not require dismantling the busbar. It can also be operated with electricity without affecting the normal power consumption of customers. It can be used in conjunction with relay protection, measurement, and metering devices.

      Application scope:

      Applied to power distribution system renovation projects.

      Ordering Example:

      Specific model: AKH-0.66/K K-80 * 50 800

      Technical requirements: Rated current ratio of 800A/5A; Accuracy level 0.5; Rated load of 2.5VA.

      Communication protocol: None

      Power supply: none

      2 Technical parameters

      AKH-0.66/K open-ended current transformer

      3 External dimensions

      AKH-0.66K - Φ Open Current Transformer

      AKH-0.66/K open-ended current transformer

      AKH-0.66K - Φ Open Current Transformer

      Technical specifications: Open type CT. Primary current 100-6300A, secondary current 5A, 1A. Rated operating voltage AC0.66kV (equivalent AC0.69kV, GB/T156-2007). Rated frequency 50-60Hz. Environmental temperature -30 ℃~70 ℃. Altitude ≤ 3000m. Power frequency withstand voltage 3000V/1min 50Hz. Suitable for places without direct rain, snow, severe pollution, or severe vibration