TT-MK-A Grounding Module Square Grounding Module Penetrating Grounding Module Physical Resistance Reducing Agent
Category:
Security/Lightning protection equipment/Other lightning protection equipment
Model:
TT-MK-J TT-MK-A
Brand:
other
model:
TT-MK-J TT-MK-A
type:
Lightning protection grounding material
lifespan:
30 years
Processing & Customization:
yes
Is it imported:
No
Item Number:
TT-MK-J TT-MK-A
Specifications:
500*400*60mm 600*400*60mm
series:
Lightning protection grounding material
manufacturer:
Qingdao Zhongdian
Retail Price
78.00USD
重量
kg
- Product Description
-
model TT-MK-J TT-MK-A
type Lightning protection grounding material
lifespan 30 years
Processing & Customization yes
Is it imported No
Item Number TT-MK-J TT-MK-A
Specifications 500*400*60mm 600*400*60mm
series Lightning protection grounding material
manufacturer Qingdao Zhongdian
Description :
Technical parameter indicators of TT-MK-A low resistance grounding module
model
Appearance (mm)
quality
Power frequency grounding resistance
Room temperature resistivity
Low resistance grounding module
500*300*80
500*400*60
23kg
≤5Ω
≤0.38Ω. m
Calculation of TT-MK-A low resistance grounding module usage
Based on years of practical experience in using grounding modules to construct grounding grids, the following formula for calculating module usage is summarized:
ρ·M
The calculation result is rounded to an integer when it is a decimal.
Rn·K
In the formula: n is the number of grounding modules.
ρ - Soil resistivity.
M - module grounding coefficient, with a value range of 0.12~0.16. The larger the soil resistivity ρ, the smaller the value of M.
Rn - Grounding resistance value of the grounding network design.
K - Utilization coefficient, with a value range of 0.7~0.85. The more modules there are, the smaller the value of K.

The relationship between the values of various coefficients can be referred to in the following table:
Soil resistivity
Grounding coefficient (M)
Utilization coefficient (K)
ρ<200Ω. m
zero point one six
zero point eight five
200≤ρ<500Ω·m
zero point one five
zero point eight
500≤ρ<1000Ω·m
zero point one three
0.75~0.8
ρ≥1000Ω·m
zero point one two
zero point seven five
Performance characteristics of TT-MK-A low resistance grounding module
(1) Corrosion resistant, non-toxic, long service life, easy installation, reducing construction workload;
(2) Capable of absorbing moisture and moisture, with low grounding resistance;
(3) The resistance to high current impact does not increase, and there is no hardening, brittleness, or fracture phenomenon;
(4) Can effectively reduce the grounding resistance of high resistance soil;
(5) The grounding resistance is less affected by the season, and the resistance value can remain stable for a long time.
AfterSalesService :
Key words:- Grounding module
More Products