Parameters/wiring of power plant specific recoverable temperature sensing cable
Category:
Security/Fire protection system/Alarm equipment
Model:
JTW-LD-HK3003
Brand:
Hongshengjia
Retail Price
0.99USD
重量
kg
- Product Description
-
Description :
Overview
The JTW-LD-HK3003 cable type linear temperature sensing fire detector (hereinafter referred to as the detector) is a recoverable fire detection product. The detector is mainly designed based on the national standard GB16280-2014 "Linear Temperature Sensing Fire Detector" of the People's Republic of China, and has the characteristics of fixed temperature fire detection and alarm. This detector consists of a temperature sensing cable, a signal processing unit, and a terminal unit. It uses a relay passive contact output and can be easily matched with fire alarm controllers from different manufacturers. It is widely used for early detection of fires in industrial settings such as metallurgy, power, and petrochemicals.
II working principle
The detector consists of a temperature sensing cable, a signal processing unit, and a terminal unit. The temperature sensing cable adopts a two core cable structure, with a core wire made of metal wire with a diameter of 0.6mm. The outer part of the metal wire is made of temperature sensing material, and the impedance between the core wires changes with the surrounding temperature; The signal processing unit is equipped with signal processing circuits, including signal acquisition, signal amplification and conversion circuits, display circuits, etc. The signal processing unit is connected to a certain length of temperature sensing cable and terminal unit for use. The signal processing unit continuously monitors the temperature sensing cable and alarms for temperature rise, wire breakage, and short circuit caused by abnormal situations.
IIIMain functional features and technical performance
1. Meet the relevant requirements of the national standard GB16280-2014 "Linear Thermal Fire Detector" of the People's Republic of China. The heating length of its motion performance is 1 meter.
2. It has a constant temperature alarm function, with a constant temperature alarm threshold of 85 ℃.
3. Use a length of ≤ 200m.
4. It has two independent passive relay contact outputs for fire alarm and fault alarm.
1. It can monitor the open circuit and short circuit faults of temperature sensing cables.
2. The temperature sensing cable has a recoverable function.
3. The temperature sensing cable adopts a twisted cable structure, which has strong resistance to mechanical damage and electromagnetic interference.
4、 Main technical parameters:
1. Alarm temperature 85 ℃± 10% 105 ℃± 10% Other temperatures can be customized
2. Operating environment temperature: -10 ℃ to 50 ℃
3. Relative humidity of the usage environment: ≤ 95%, no condensation
4. Working voltage:
5. Static monitoring current: ≤ 25mA when the working voltage is 30V
≤ 40mA when the working voltage is 24V
≤ 90mA when working voltage is 10V
6. Alarm state current: ≤ 40mA when the working voltage is 30V
≤ 70mA when working voltage is 24V
≤ 160mA at a working voltage of 10V
7. Self recovery fuse: 350 mA
8. Fire alarm output form: Relay (closed upon alarm) output
Fault output form: Relay conversion contact output
9. Relay contact capacity: 1A/24VDC
10. External dimensions:
External dimensions of signal processing unit (length x width x height): 160.0mm x 100.0mm x 64.5mm
Terminal unit dimensions (length x width x height): 80mm x 82mm x 56mm
11. Shell protection level: IP65


AfterSalesService :
Key words:- Recoverable temperature sensing cable